RE-Y(st)Y-PiMF/TiMF, shielded pairs - 300/500 V

Application

RE-Y(st)Y-PiMF/TiMF is used for process control and data processes, analog or digital transmission; instrumentation cables are used for a wide range of areas. Factories, refineries, petrochemical institutions, energy houses, natural gas pump stations, ect. are the general use of the cables.

Construction

Conductor

Blank, tempered, stranded Cu

Insulation

PVC

Conductor color

Pair: black/white, numbered
Triple: black/white/red, numbered

Screen

shielded pairs: AL/PES tape (0.60mm2 tinned Cu with drain wire)
Overall shielding: AL/PES tape (7x0.3mm2 tinned Cu with drain wire)

Outer sheath

PVC, black or blue

Technical data

Working temperature

-30º C to +70º C

Rated voltage

300/500 V

Test voltage

Conductor/screen: 1000 V, conductor/conductor: 2000 V

Bend radius

7,5 x cable diameter

Approvals

EN 50288-7, VDE 0815, VDE 0816, BS5308 afsnit 1 og 2, IEC 60332-1, IEC 60332-3-24, CE, RoHS
Bending radius 7,5 x cable diameter
Fire retardant acc. to IEC 60332-3
Flame retardant acc. to IEC 60332-1
SKU EAN Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
10420075 5704403081868 20x2x0,75 - D./Cut 21,90 662