N2XS2Y 1-conductor, Cu - 12/20 (24) kV

Application

N2XS2Y is used for installations indoor as well as outdoor, above or directly in the ground, in tubes or water.

Construction

Conductor

Round Cu threads, class 2
Semi conducting layer around the conductor

Insulation

XLPE insulated
Semi conducting layer around the insulation

Filling sheath

Tape of conductive material

Screen

Cu threads over tape material

Outer sheath

PE, black

Technical data

Working temperature

-20° C to +90° C

Rated voltage

12/20 kV (24 kV)

Test voltage

42 kV

Bend radius

15 x cable diameter

Approvals

IEC 60502, CE, RoHS
Bending radius 15 x cable diameter
Can be buried
For use in wind turbines
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -20° C
UV-resistant
SKU EAN Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
871011366 - 1X35/16 200 D./Cut 28 970
871011367 - 1X50/16 239 D./Cut 29 1150
871011368 - 1X70/16 297 D./Cut 31 1350
871011369 - 1X95/16 361 D./Cut 32 1650
871011370 - 1X120/16 416 D./Cut 34 1900
871011371 - 1X150/16 470 D./Cut 35 2150
871011372 - 1X150/25 470 D./Cut 35 2250
871011373 - 1X185/16 538 D./Cut 37 2550
871011374 - 1X185/25 538 D./Cut 37 2600
871011375 - 1X240/16 634 D./Cut 40 3100
871011376 5704403056019 1X240/25 634 D./Cut 40 3200
871011377 - 1X300/25 724 D./Cut 42 3800
871013215 - 1X300/35 724 D./Cut 42 3850
871011378 - 1X400/35 829 D./Cut 45 4750
871011379 - 1X500/35 953 D./Cut 48 5800
871013154 - 1X630/35 1120 D./Cut 53 7090